Teamwork Initial Configuration - Huawei FusionModule1000A40 Commissioning Manual

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide

8.2.3 Teamwork Initial Configuration

Prerequisites
You have powered on the air-cooled smart cooling products.
Preparations
Tools: none
Documents: cooling device initial configuration table, cooling product teamwork relationship
diagram, management system initial configuration table
Skill requirement: cooling engineer
Context
Teamwork is a solution for allocating the overall temperature and humidity of the
FusionModule1000. It is used to improve the operating efficiency of smart cooling products
by preventing competitive operations.
Multiple smart cooling products are interconnected and centrally controlled to support the
rotation of active and standby smart cooling products. A maximum of 32 smart cooling
products can be interconnected using the CAN bus. The smart cooling product whose address
is displayed as 1 on the LCD is the master, which collects, processes, and delivers data.
Figure 8-8
Figure 8-8 Teamwork topology
Issue 04 (2020-01-17)
Air-cooled smart cooling products include 21 kW and 25 kW models.
For the diagrams and tables, see the initial configuration parameter manual for the solution
in use.
shows the teamwork topology for air-cooled smart cooling products.
Copyright © Huawei Technologies Co., Ltd.
8 Commissioning Core Components
56