FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
Table 8-4 Note for the screen
No.
1
2
3
4
5
Issue 04 (2020-01-17)
Option
ON/OFF/NA
01/02/03/04
Active/Standby
Frame:
green/non-green
Background color:
red/bright gray/dark
gray
Copyright © Huawei Technologies Co., Ltd.
Remarks
ON indicates that the smart cooling product is started,
OFF indicates shutdown, and NA indicates offline.
Indicates the device address. 01 is the master unit and
others are all slave units. If the master unit is offline,
teamwork networking fails.
Active: An active unit properly responds to control
requirements.
Standby: A standby unit responds to control requirements
only if an active unit is faulty (emergency alarm,
shutdown, or offline) or the active units cannot meet
cooling requirements.
A device with a green frame indicates the device itself,
as shown in
Devices without a green frame indicate other devices in
the teamwork group,
as shown in
Red background color indicates that an emergency alarm
is generated,
as shown in
Bright gray background color indicates that no
emergency alarm is generated,
8 Commissioning Core Components
.
.
.
57