Commissioning The Logic Load Disconnection (Powering-Off) Of The Power Supply System Under Normal Temperature - Huawei FusionModule1000A40 Commissioning Manual

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
Step 4 Remove the other power plug for the server or switch off the corresponding rPDU input
circuit breaker in the PDC.
Step 5 Power on the server 30s later. Check that the server works properly and does not restart or
break down.
----End
7.1.2 Commissioning the Logic Load Disconnection
(Powering-Off) of the Power Supply System Under Normal
Temperature
Prerequisites
The FusionModule1000 is powered on, commissioned, and working properly.
Preparations
Tools: none
Documents: power supply and distribution system diagrams, power supply and distribution
device layout diagram
Skill requirement: power distribution engineer
Procedure
Step 1 Power off the FusionModule1000.
1.
2.
3.
4.
Step 2 Verify whether the system and devices are intact and working properly.
Issue 04 (2020-01-17)
When the server switches between the two power supplies, if the server does not restart, break down, or
generate any alarm (except power failure alarms), the power supply switchover meets the requirements.
For the diagrams and tables, see the initial configuration parameter manual for the solution in use.
Save parameters before power-off.
Power off the devices in the normal power-off logic sequence.
During the power-off process, there is no fire or other exceptions, but the extinguishant
control panel displays a power failure alarm. Ignore the alarm.
After power-off, all circuit breakers should be OFF.
Shut down servers and storage devices.
Shut down cooling products.
Switch off circuit breakers level by level to power off devices by referring to the power
supply and distribution system diagram.
Switch off the external input power circuit breaker of the FusionModule1000.
Copyright © Huawei Technologies Co., Ltd.
7 System Commissioning
31