Huawei FusionModule1000A40 Commissioning Manual page 34

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
System
Check Item
Access control
system
Fire extinguishing
Extinguishant
system (CE)
control panel
Smoke detector
Heat detector
Emergency light
Fire alarm bell
Extinguishant abort
button
Pneumatic switch
Electrical actuator
Horn strobe
Warning sign
(Optional) VESDA
VESDA power box
Issue 04 (2020-01-17)
Check Sub-item
WiFi converter
T/H sensor
Pre-fab. module door
Indicators on the
extinguishant control panel
Indicator
Indicator
Power indicator
Alarm indicator on the
extinguishant control panel
VESDA power-on
commissioning
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Criteria
The RUN and WiFi indicators are
on, and the WPS indicator is off.
The sensor displays the temperature
and humidity values.
The magnetic lock indicator is
green when the pre-fab. module
door is closed.
The magnetic lock indicator is
red when the pre-fab. module
door is open.
The pre-fab. module door can be
opened from outside the pre-fab.
module using an access card,
and door opening operations are
logged in the management
system.
The pre-fab. module door can be
opened from inside the pre-fab.
module using the exit button,
and door opening operations are
logged in the management
system.
Indicators on the extinguishant
control panel:
The power indicator is on.
The alarm indicator is off.
The indicator blinks once every 6s.
The indicator blinks once every 6s.
The power indicator is on.
The alarm indicator is off.
The VESDA power indicator is on,
and there is no alarm in the
management system.
28