Huawei FusionModule1000A40 Commissioning Manual page 68

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
Parameter
Description
by the master unit.
When Requirement control is
set to Disable, the master unit
does not synchronize operating
data to slave units, and all the
cooling products operate based on
their own requirements, not
referring to the mode delivered by
the master unit.
Cascade
If requirement control is enabled, you
can enable the cascade function to
start standby units if running units
cannot meet the cooling capacity
requirement.
Large ring
Proportion coefficient in L1/L2
cooling
linkage PID control
capacity P
Large ring
Integration coefficient in L1/L2
cooling
linkage PID control
capacity I
Large ring
Differential coefficient in L1/L2
cooling
linkage PID control
capacity D
Cooling
Adjustment period in L1/L2 linkage
capacity
PID control
adjustment
period
L1/L2 linkage
Reference temperature at which the
cooling stop
cooling product stops cooling in the
ref. temp
cooling mode in L1/L2 linkage.
L1/L2 linkage
Reference temperature at which the
dehumid stop
cooling product stops
ref. temp
dehumidification in the
dehumidification mode in L1/L2
linkage.
L1/L2 linkage
Duration within which the device is
cooling stop
still cooling when the cooling stop
delay
condition is met in L1/L2 linkage.
L1/L2 linkage
Maximum temperature rise rate when
fastest temp
the temperature rises rapidly caused
rise
by sudden load power increase.
Issue 04 (2020-01-17)
Configuration Principle
If the heat load of devices may
increase, it is recommended that you
enable the cascade function.
You are not recommended to change
the value.
You are not recommended to change
the value.
You are not recommended to change
the value.
You are not recommended to change
the value.
Set this parameter based on the lowest
temperature allowed onsite. Normally
you are not recommended to change
the default value.
Set this parameter based on the lowest
temperature allowed onsite. Normally
you are not recommended to change
the default value.
Set this parameter based on the lowest
temperature allowed onsite. Normally
you are not recommended to change
the default value.
Set this parameter based on the
micro-module size and maximum load
power. The smaller the module and the
higher the load power, the greater the
temperature rise rate is.
Copyright © Huawei Technologies Co., Ltd.
8 Commissioning Core Components
Default
Value
Disable
0.10
350s
10s
5s
18.0° C
18.0° C
18s
4.0° C/min
62