Huawei FusionModule1000A40 Commissioning Manual page 58

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
Preparations
Tools: none
Documents: 21 kW air cooled smart cooling product user manual, 25 kW air cooled smart
cooling product user manual, power supply and distribution system diagram, cooling device
layout diagram
Skill requirement: cooling engineer
Procedure
Step 1 Switch on the input power circuit breakers for the air cooled smart cooling product indoor
units in the upstream PDC, and switch on fan circuit breakers QF5–QF10 in the electric
control box for the cooling product indoor units to power on the cooling product indoor units.
Step 2 Switch on circuit breaker QF3 for the outdoor unit in the electric control box for the air cooled
smart cooling product indoor units to power on the cooling product outdoor units.
Step 3 Verify the initial configuration of the air cooled smart cooling product.
Issue 04 (2020-01-17)
Cooling products that use power crossfeed can be powered on only after both power inputs
are connected.
Teamwork settings can be performed only after all cooling products in a group have been
powered on.
Air cooled smart cooling products include 21 kW and 25 kW models.
For the diagrams and tables, see the initial configuration parameter manual for the solution
in use.
Before the power-on commissioning, ensure that the air supply and return vents of cooling
products are not blocked.
The humidifier water refill and drainage work properly, and cooling product condensate
drainpipes are intact and not blocked.
If any alarm is raised, rectify the fault before continuing the commissioning.
Before power-on, clear dust, dirt, and foreign matter from the cabinet; otherwise, the water
pump may be blocked, resulting in drainage failure or serious equipment malfunction.
Copyright © Huawei Technologies Co., Ltd.