3.4.5 Fire Extinguishing System (CE Kidde)

Issue 04 (2018-01-05)
Check
Operation
Standard
If the
temperature
exceeds the
alarm
threshold, the
gas release
indicator turns
on. The fire
alarm control
panel
generates an
alarm and
triggers the fire
alarm sounder.
Release smoke
If the smoke
onto the smoke
density is
detector using a
below the
smoke pistol.
alarm
threshold, the
alarm indicator
blinks once
every 6s.
If the smoke
density
exceeds the
alarm
threshold, the
indicator turns
on. The fire
alarm control
panel
generates an
alarm and
triggers the fire
alarm sounder.
Unlock the fire
The fire alarm
alarm control panel
horn/strobe
and press
generates
HORN/STROBE.
glaring flashes
and shrill
alarms.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Maintenance
Troubleshooting
Replace the heat detector if the fault
persists.
Replace the smoke detector
Replace the smoke detector if the
fault persists.
1. Check cables connected to the
fire alarm control panel. If a
short circuit or open circuit is
identified, reconnect the cables.
2. Replace the indoor fire alarm
horn/strobe if the fire alarm
horn/strobe does not react.
34