4.13 Mains Outage Alarm

Fault
Category
Mains
outage
Issue 04 (2018-01-05)
Alar
Symptom
m
Sever
ity
The water sensor is
covered by
condensate water.
Condensate water
cannot be drained.
Alar
Symptom
m
Sever
ity
Major
The
FusionModule1000
is power off.
The DG cannot be
started.
A circuit breaker
cannot be operated,
or an action does not
take effect.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Troubleshooting
Cause
The
Replace the dehumidifier
dehumidifier
drainpipe.
drainpipe is
damaged.
The thermal
Replace the thermal
insulation layer
insulation foam.
is damaged.
The humidity is
Dehumidify the
too high.
FusionModule1000
using a dehumidifier.
The condensate
Remove foreign matters
drainpipe is
using a thin iron wire or
blocked or
remove the ice.
frozen.
Possible
Troubleshooting
Cause
The mains
Switch to another mains
supply is cut
or DG.
off.
A dry contact is
Check the dry contact.
faulty.
The DG startup
Contact Huawei
failed.
technical support.
The PDC circuit
Contact Huawei
breaker is
technical support.
faulty.
4 Alarms and Faults
56