Huawei FusionModule 1000A40 Maintenance Manual page 155

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
2.
3.
Step 5 Remove the pressure operated switch hose from the container valve of the fire cylinder.
Step 6 Remove the screws securing the fire cylinder using a Phillips screwdriver, and remove the fire
cylinder fasteners.
Step 7 Remove the faulty fire cylinder from the installation position.
Step 8 Move the new fire cylinder to the installation position, and tighten the fire cylinder fasteners.
Keep the pressure gauge panel outwards so that people can view the reading.
Step 9 Connect the hose to the pressure operated switch.
Wrap the threads with sealing tape to ensure air tightness.
Step 10 Connect the fire cylinder to the fire extinguishing pipeline.
Issue 04 (2018-01-05)
Figure 5-76 Disconnecting the fire cylinder and fire extinguishing pipeline
Remove the I-shaped connection pipe.
Remove the threaded adapter from the container valve of the fire cylinder, as shown by
(2) in
Figure
5-76.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Components Replacement
147