Huawei FusionModule 1000A40 Maintenance Manual page 119

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Procedure
Step 1 Switch off the active and standby power supplies to the fire alarm control panel.
Step 2 Remove the screws shown in
Figure 5-36 Removing the screws
Step 3 Remove the cables using a flat-head screwdriver and label the cables.
Step 4 Remove the screws on the base using a Phillips screwdriver, and remove the base.
Step 5 Install the new base in the same position.
Step 6 Reconnect cables in the same way.
Step 7 Secure the panel to the base.
Step 8 Switch on the active and standby power supplies to the fire alarm control panel.
Step 9 Check whether the new gas release indicator is working properly.
1.
2.
Issue 04 (2018-01-05)
For the diagrams, see the initial configuration parameter manual for the solution in use.
Before replacing the gas release indicator, inform the related administrative departments of
the temporary downtime of the fire extinguishing system. After the replacement, inform
the administration department that the system has become operational.
Disconnect the red and black cables from the pressure announciator, as shown by (1) in
Figure
5-37.
Short-circuit the cables from the fire alarm control panel to the pressure announciator, as
shown by (2) in
Figure
If the gas release indicator turns on, the gas release indicator is working properly.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure 5-36
using a Phillips screwdriver, and remove the panel.
5-37.
5 Components Replacement
111