3.2.3 Monitoring System

Table 3-4 Monthly maintenance checklist for the monitoring system
Item
Event and
operation
logs in the
RH2288
server
ECC500
collector
VCN500
indicator
Issue 04 (2018-01-05)
Expected
Method
Result
The refrigerant
pipe support is
secure and
intact.
Check the thermal
The thermal
insulation foam.
insulation
foam is in
good condition
and free from
condensation.
Method
Expected
Result
Choose System
Normal system
Event Log in the
events are
navigation tree.
displayed.
Check the
The running
indicators of the
indicator is
ECC500 main
steady on.
control module.
Check the
The VCN500
VCN500 indicator.
indicator is
steady green.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Maintenance
Troubleshooting
If the pipe support is worn out or
not properly fixed, replace and
tighten the support by following
instructions in NetCol5000-A 20 kW
Air-Cooled In-Row Precision Air
Conditioner User Manual.
If there is condensation under a
pipe, replace the thermal insulation
foam.
Troubleshooting
If a system event exception is found,
troubleshoot by referring to
documents delivered with the
RH2288 server.
If the running indicator blinks at
short intervals, check that power
supply of the ECC500 collector
is normal, and check that the
communications cable between
the ECC500 and the host is
properly connected.
If the alarm indicator is on, view
and handle the alarms.
If the indicator is in an abnormal
status, troubleshoot by following
instructions in VCN500 Product
Documentation.