Maintenance Guide (2016.05, AI Version)

6.1 Emergency Operations for Mains Failure

Prerequisites
The mains supply to the FusionModule1000 is faulty.
Context
The FusionModule1000 power supply and distribution system supports the following power
supply modes:
Procedure
Step 1 Check whether the UPS is working properly.
Step 2 Check whether the ATS in the mains bus coupler cabinet switches to the other mains supply
or the DG.
Issue 04 (2018-01-05)
One mains supply and one DG
Two mains supplies
Perform emergency operations based on the power supply mode used by the FusionModule1000.
If the switchover fails, manually start the DG within 5 minutes after the power outage
occurs. If the DG still cannot be started, back up data immediately.
If the DG starts and supplies power normally, find the cause of the power outage and the
DG backup time as soon as possible. If the DG can supply power until the mains supply is
restored, prepare for the subsequent power supply switchover. If the power provided by
the DG cannot sustain to the time the mains supply is restored, back up the data
immediately.
If the ATS switchover is working properly, check whether all devices are working
properly.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6

Emergency Operations

6 Emergency Operations
177