Other Systems - Huawei FusionModule 1000A40 Maintenance Manual

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Device
Emergency
light
Smoke
detector
Heat
detector

3.2.7 Other Systems

Table 3-8 Monthly maintenance checklist for other systems
Maintena
nce Item
Pre-fab.
module
paint
Pre-fab.
module
external
environmen
t
Issue 04 (2018-01-05)
Operation
Check Standard
fire extinguishing
All devices of the
pipeline, and
fire extinguisher are
nozzle.
free from rust on the
exterior, and the
coating is intact.
The lead seal and
safety signs on
hand-operated
devices of the fire
cylinder are intact.
Check the pressure
The pressure pointer
pointer of the fire
is in the green zone.
cylinder.
Disconnect the
The emergency light
power plug of the
turns on.
emergency light.
Check the smoke
The indicator blinks
detector indicator.
once every 6s.
Check the heat
The indicator blinks
detector indicator.
once every 6s.
Operation
Standards
Compliance
Check the
The pre-fab.
appearance of the
module and
pre-fab. module.
bases are free
from paint
flake-off, rust,
or corrosion.
Check the pre-fab.
No hazard or
module external
potential
environment.
hazard exists
around the
pre-fab.
module.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Maintenance
Maintenance Guide
Repaint.
Replace the electrical
actuator.
Ask a fire engineer to check
whether the fire cylinder leaks
extinguishant. If leakage
occurs, the fire engineer
charges the extinguishant in
the local charging station.
Replace the emergency light.
Replace the smoke detector.
Replace the heat detector.
Troubleshooting
If any part of the pre-fab. module is
damaged or corroded, maintain or
replace the damaged and corroded
part.
If there is potential hazard or
pollutant around the pre-fab.
module, take workaround measures.
17