Replacing A Dehumidifier - Huawei FusionModule 1000A40 Maintenance Manual

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Skill requirement: cooling engineer
Procedure
Step 1 (Optional) Use the ESD floor suction plate to open the aisle floor where a condensate
drainpipe needs to be replaced.
Step 2 Remove the water inside the pre-fab. module using a sucker and vessel.
Step 3 Remove all fasteners and the thermal insulation foam from the condensate water pipe.
Step 4 Remove the condensate drainpipe from the precision air conditioner, and block the condensate
drainage port using a rubber plug.
Step 5 Remove the other end of the condensate drainpipe.
Step 6 Take out the rubber plug and install a new condensate drainpipe.
Step 7 Check that the new condensate drainpipe is working properly.
Step 8 Dry the drainpipe using the dry rag, and wrap the thermal insulation foam.
Step 9 (Optional) Reinstall the aisle floor.
----End
Follow-up Procedure
Dispose of the removed condensate drainpipe that is confirmed faulty.

5.2.6.3 Replacing a Dehumidifier

Prerequisites
Impact on the System
None
Preparations
Tools: Phillips screwdriver, flat-head screwdriver, protective gloves, ESD floor suction plate
Issue 04 (2018-01-05)
For the diagrams, see the quick installation guide for the solution in use.
Wipe off the water with a dry cloth if there is not much water.
Hold the removed drainpipe properly to prevent residual water from flowing out into the pre-fab.
module.
If there is no water in the condensate water pan, the condensate drainpipe is working properly.
A dehumidifier is faulty.
A spare dehumidifier of the same model is available and functional.