Maintenance Guide (2016.05, AI Version)
Figure 5-45 Securing the fixing plate
Step 7 Switch on the standby power supply to the fire alarm control panel.
Step 8 Check that the new batteries are working properly.
----End
Follow-up Procedure
Dispose of the removed fire alarm control panel batteries that are confirmed faulty.

5.4.8 Replacing a Fire Cylinder (Standard)

Prerequisites
A spare fire cylinder of the same model is available and functional.
Impact on the System
The fire extinguishing system stops working during the replacement.
Preparations
Tools: pallet truck, Phillips screwdriver, protective gloves, adjustable wrench
Materials: spare fire cylinder, sealing tape
Documents: fire extinguishing device layout diagram (standard)
Skill requirement: fire engineer
Issue 04 (2018-01-05)
If the BATTERY FAULT indicator on the fire alarm control panel is off, the new batteries are working
properly.