Fire Extinguishing System (Ce Kidde) - Huawei FusionModule 1000A40 Maintenance Manual

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Device
Smoke
detector
Heat
detector

3.2.5 Fire Extinguishing System (CE Kidde)

Table 3-6 Monthly maintenance checklist for the fire extinguishing system
Device
Extinguisha
nt control
panel
Extinguisha
nt control
panel
batteries
Fire
extinguishe
r
Issue 04 (2018-01-05)
Check
Operation
Standard
Unplug the input
The
power supply.
emergency
light turns on,
the power
indicator turns
off, and the
fault indicator
turns off.
Check the smoke
The indicator
detector indicator.
blinks once
every 6s.
Check the heat
The indicator
detector indicator.
blinks once
every 6s.
Check
Operation
Standard
Check indicators
The power
on the
indicator turns
extinguishant
on, and the
control panel.
alarm indicator
turns off.
Check the battery
The wiring
terminals.
terminals are
in good
condition
without
corrosion.
Check the
All devices of
appearance of the
the fire
fire cylinder,
extinguisher
electric control
are intact, free
head, pressure
from
operated switch,
deformation
fire extinguishing
and
pipeline, and
mechanical
nozzle.
damage.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Maintenance
Troubleshooting
Replace the emergency light.
Replace the smoke detector.
Replace the heat detector.
Troubleshooting
Replace the extinguishant control
panel.
Clean the contaminated and
corroded terminals. Replace the
batteries with severely corroded
terminals for the fire alarm control
panel..
Replace the fire cylinder. For details
about how to replace other devices,
contact Huawei technical support.