Huawei FusionModule 1000A40 Maintenance Manual page 113

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
1.
2.
3.
4.
5.
Step 3 Take out a new access controller, and set the DIP switch for the access controller to set its
address by referring to the management system initial configuration table.
Figure 5-31 Position of the access controller DIP switch
Step 4 Install the new access controller and reconnect the terminal blocks and network cable.
Step 5 Secure the access controller.
Step 6 Switch on the power circuit breaker of access controller, and configure the access card
permission by referring to the NetEco commissioning guide.
Step 7 Verify that the access controller works properly.
----End
Follow-up Procedure
Dispose of the removed access controller that is confirmed faulty.
Issue 04 (2018-01-05)
Remove the terminals on the right side of the access controller.
Remove the terminals on the left side of the access controller.
Remove the network cable on the top of the access controller.
Use a Phillips screwdriver to remove the four screws that fasten the access controller.
Remove the lower screws and then the upper ones.
Push the access controller upwards and remove it.
Install terminals on the left and right of the access controller based on the mapping between cable labels
and the silk screens on the access controller.
The access controller is working properly if the pre-fab. module door can be opened from outside using
an access card and from inside using the exit button, and the door opening operation is logged in the
monitoring system.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Components Replacement
105

Advertisement

Table of Contents
loading

Table of Contents