4.11 Access Alarm

Fault
Category
Access
alarm

4.12 Water Intrusion Alarm

Fault
Category
Water
Intrusion
Alarm
Issue 04 (2018-01-05)
Alar
Symptom
m
Sever
ity
Critica
The door status
l
cannot be controlled.
The access card
cannot be read.
Alar
Symptom
m
Sever
ity
Gener
There is no water
al
onsite.
There is water
onsite.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Troubleshooting
Cause
The access
Verify the access
controller is
controller cable
faulty.
connections, or replace
the access controller.
The access card
Prepare a new access
is damaged.
card and assign the
access permission.
The card reader
Verify the card reader
is faulty.
cable connections, or
replace the end door card
reader.
Possible
Troubleshooting
Cause
The water
Replace the water sensor
sensor is faulty.
(point type).
A pipe is
Contact Huawei
damaged.
technical support.
A humidity
Replace the humidifier
water refill pipe
water refill pipe for a
is damaged.
precision air conditioner.
The condensate
Replace the condensate
drainpipe is
drainpipe of a precision
damaged.
air conditioner.
The condensate
Remove the drainpipe
drainpipe is
outside the pre-fab.
blocked.
module, and dig out the
material blocking the
pipe using a thin iron
wire.