Huawei FusionModule 1000A40 Maintenance Manual page 158

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Figure 5-78 Removing the extinguishant control panel
Step 6 Install the new extinguishant control panel in the same position.
Step 7 Put the corrugated pipes and cables back to the box, and reconnect the cables according to
labels.
Step 8 Put the batteries to the same position.
Step 9 Switch on the input circuit breaker of the extinguishant control panel, and connect the battery
cables to the extinguishant control panel.
Distinguish the positive and negative battery terminals when connecting battery cables.
Figure 5-79 Connecting battery cables
Step 10 Check whether the new extinguishant control panel is working properly.
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Components Replacement