Shutting Down And Powering Off The System - Huawei PowerCube 5000 Quick Manual

Hide thumbs Also See for PowerCube 5000:
Table of Contents

Advertisement

8

Shutting Down and Powering Off the System

The output load is transferred or there is no major load so that system power-off is allowed. Once
the system is shut down, there is no power output from the output end.
Tap the start/stop button
on the main menu of the MDU in the ICC cabinet
to disconnect the system output.
Turn off the AC output switch and isolation transformer disconnector.
Turn off the battery breaker QF1 in each lithium battery cabinet.
Turn off the solar input switch and AC input switch.
Check that the loads have powered off completely and that the control panel
and indicators have turned off.
Huawei Technologies Co., Ltd.
Huawei Industrial Base, Bantian, Longgang
Shenzhen 518129 People's Republic of China
www.huawei.com
24

Advertisement

Table of Contents
loading

Table of Contents