Replacing The Gas Release Indicator (Standard) - Huawei FusionModule 1000A40 Maintenance Manual

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Figure 5-35 Heat detector installation reference line
Step 7 Power on the fire alarm control panel after verifying that the new heat detector is properly
installed.
Step 8 Check whether the new heat detector is working properly.
----End
Follow-up Procedure
Dispose of the removed heat detector that is confirmed faulty.

5.4.3 Replacing the Gas Release Indicator (Standard)

Prerequisites
A spare gas release indicator of the same model is available and functional.
Impact on the System
The fire extinguishing system stops working during the replacement.
Preparations
Tools: Phillips screwdriver, protective gloves, step ladder, flat-head screwdriver
Materials: spare gas release indicator
Documents: fire extinguishing device layout diagram (standard)
Skill requirement: fire engineer
Issue 04 (2018-01-05)
If the red indicator blinks once every 6s, the heat detector is working properly.