RPV311 AC and DC Power Connection

RPV311-TM-EN-7

Figure 104: Pre-insulated tubular pin terminals

The pin terminals should be completely inserted into the header connector supplied
with the unit so that no metallic parts are exposed, as shown in Figure 105.

Figure 105: Header connector assembly

A safety ground lead shall be connected to the terminal marked with the protective
earth symbol.
For better electromagnetic compatibility, ground the unit using a 10 mm (0.4 in) wide
grounding strap to connect the back panel of the unit to a good grounding point on
the mounting rack.
Figure 106
show the wiring diagram for the AC and DC of the RPV311 respectively.

Figure 106: AC/DC power connection

For compliance with IEC 61010, install a suitable external switch or circuit breaker in
each current-carrying conductor of RPV311 power supply; this device should
interrupt both the hot (+/L) and neutral (-/N) power leads. An external 10 A, category
C, bipolar circuit-breaker is recommended. The circuit breaker should have an
interruption capacity of at least 25 kA and comply with IEC 60947-1 and IEC 60947-3.
Chapter 15 – Installation