Dismantling The Goods; Normal Use Of The Equipment; Mounting The Device; Rpv311 Mechanical Installation - GE RPV311 Technical Manual

Distributed multifunction fault recorder
Table of Contents

Advertisement

Chapter 15 – Installation
1.4

Dismantling the Goods

2

Normal Use of the Equipment

3

Mounting the Device

3.1

RPV311 Mechanical Installation

RPV311-TM-EN-7
for regeneration will depend on the size of the bag. If a ventilating, circulating oven is
not available, when using an ordinary oven, open the door on a regular basis to let
out the steam given off by the regenerating silica gel.
On subsequent unpacking, make sure that any dust on the carton does not fall inside.
Avoid storing in locations of high humidity. In locations of high humidity the
packaging may become impregnated with moisture and the de-humidifier crystals
will lose their efficiency.
The device can be stored between –25º to +70ºC for unlimited periods or between -
40°C to + 85°C for up to 96 hours (see technical specifications).
If you need to dismantle the device, always observe standard ESD (Electrostatic
Discharge) precautions. The minimum precautions to be followed are as follows:
Use an antistatic wrist band earthed to a suitable earthing point.
Avoid touching the electronic components and PCBs.
In order to maintain the equipment integrity, levels of protection and assure user
safety, the RPV311 and RA33x shall be installed in an enclosed panel with
recommended ingress protection rating of IP42 or above. The Reason range of
equipment shall be kept in an environment where their rear connection and sides are
protected against impact and water. The enclosing panel shall ensure that the
equipment rear connections are not exposed, meanwhile maintaining adequate
temperature and humidity condition for the devices. Furthermore, the equipment
shall have all their rear connectors attached, even if not being used, in order to keep
their levels of ingress protection as high as possible.
The RPV311 and RA33x modules are IEC 61010-1 rated at Installation/Overvoltage
Category II and Pollution Degree 3. These ratings allow mounting of the equipment
indoors or in an outdoor (extended) enclosure where the equipment is protected
against exposure to direct sunlight, precipitation, and full wind pressure.
During the normal use of the device only its the frontal panel shall be accessible.
The RPV311 must be installed in a 19-inch rack.
The RPV311 must be installed at least 10 cm away from any other equipment to
avoid obstruction of air circulation impairing the cooling efficiency.
RPV311
215

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents