Chapter 12 – RPV Tools
RPV311-TM-EN-7
The configuration file can be changed during the scanning process. The update
will occur in the next scanning cycle, after the waiting time.
Once the file is configured, scanning will be performed following the configuration
of the file whenever the Scanner is started.
Example of a configuration file with RPV:
Below is the configuration of the xml file with an interval of 300 seconds between
the cycles.
First RPV: activated scanning, RPV 192.168.0.195, waiting time for connection of 60
seconds, scanning fault, disturbance, steady state and SOE records, no baud rate
limit, automatic deletion of records, activated modem, telephone number for
connection to the modem 21080 300;
Second RPV: activated scanning, RPV 192.168.0.199, waiting time for connection of
60 seconds, scanning fault records, no baud rate limit, automatic deletion of records,
no modem.
<?xml version="1.0" encoding="UTF-8"?>
<scanner>
<interval>300</interval>
<list>
<equipment enabled="yes >
<address>192.168.0.195</address>
<timeout>60</timeout>
<records>
<record>fault</record>
<record>disturbance</record>
<record>steadystate</record>
<record>soe</record>
</records>
<bandwidth>0</bandwidth>
<delete>yes</delete>
<modem enabled="yes">
<phonenumber/>21080300</phonenumber>
</modem>
</equipment>
<equipment enabled="yes">
<address>192.168.0.199</address>
automatically
RPV311
168