Figure 41: Relay Signaling Events Configuration Section - GE RPV311 Technical Manual

Distributed multifunction fault recorder
Table of Contents

Advertisement

Chapter 4 – Configuration
88

Figure 41: Relay signaling events configuration section

A The L
events text field allows user to enter a code used for signaling events.
OG
Refer to
Appendix A
in the On time configuration (previous section). In order to combine several LOG
events to trigger the alarm, use "comma" to separate the LOG numbers, for instance:
709, 710.
B The W
check box allows user to select the following events for signaling:
ARNINGS
Equipment not ready;
Primary power failure;
Equipment unsync;
Fault recorder lack of memory;
Disturbance recorder lack of memory;
Steady-state recorder lack of memory;
SOE recorder lack of memory;
Link communication failure;
Internal failure.
In this case, signaling is active while the problem that has generated the alarm is not
resolved.
for log references. The relays will stay closed during the time set
RPV311
RPV311-TM-EN-7