1.3

Communication Ports, Transmission Rates

1.4

Timestamp

1.5

Configuration

1.6

Standards Compliance

2
WMU – Waveform Measurement Unit
RPV311-TM-EN-7
Each stream of data is transmitted through a particular UDP/IP port listed in the table
below:
Stream of data
1
2
3
4
The transmission rate options at 60Hz are: 10, 12, 15, 20, 30, or 60 frames per second
At 50Hz the rates are: 10, 25, or 50 frames per second.
The reported timestamp is synchronized to the UTC second rollover and refers to the
middle of the sampling window.
The PMU configuration is carried out through the Web Interface. For details about the
PMU configuration, see Chapter 4: Configuration.
The RPV311 PMU complies with the following standards:
IEEE C37.118-2005
IEEE C37.118.1-2011
IEEE C37.118.2-2011
IEEE C37.118.1a-2014
Chapter 8 – PMU
Port number
4713
4714
4715
4716