Equipment Log

RPV311-TM-EN-7
The equipment log contains information about:
Threshold violations, fault and disturbance triggers and data recording;
Data record transfer (including the IP address to which data has been
transferred);
Access to the unit's configuration pages (including IP address of which the
access was performed);
Alarms and the results of auto-diagnosis routines;
Power-up and shutdown.
The equipment log cannot be erased by the user. Its capacity is enough for
approximately 5 years of typical use, with past events being erased if memory space
is needed.
Log
Event
000
Internal failure
001
Invalid key
010
Power up
011
Power off
012
Auto power-off (primary
power failure)
Emergency power-off
013
(low battery)
020
Primary power OK
021
Primary power NOK
Appendix A – Equipment Log
Cause
Hardware or processing failure
The key applied to the
equipment is not valid
Equipment power-up
Equipment power-off
Battery operated power time
run-out
Battery charge below expected,
equipment shut off
automatically
Primary power supply voltage
equipment
Battery backup equipment