1.9

DC Transducer Inputs

1.10

Binary Inputs

DR60-TM-EN-2A
Input Isolation
>3,5 kV
¹ - Gauging performed using waveform measurement
Characteristic
Measurement
range
Accuracy
Impedance
Nominal Voltage (��
)
��
Level low
Level High
Impedance
Burden V
n
Continuous Overload
Maximum Overload (1 s)
Acquisition sampling rate
>3,5 kV
DC Transducer inputs specifications
Voltage transducer input
- 12,5 to + 12,5 V
± 0.1 % of FS magnitude
range
> 5 kΩ
Binary Inputs
125 / 250 V
65 V
91 V
120 kΩ
< 0.14W@125V
< 0.65W@250V
300 V
460 V (4 x ��
)
��
256 and 512 spc
DR60
>3,5 kV
Current transducer input
0 to 25 mA
± 0,1 % of FS magnitude
range
10 Ω
24 / 48 V
8 V
13 V
14 kΩ
< 0.06W@24V
< 0.18W@48V
100 V
460 V (4 x ��
)
��
256 and 512 spc