Chapter 6 – Records
1.5

Trigger Burst Limiter

2

Continuous and Trigger'd Disturbance Records

134

Figure 71: Example of an event without concatenation

There is an user-configurable trigger burst limiter for the fault recorder.
The burst limiter is based on the number of triggers time interval (both parameters
are user-configurable). When the limit is exceeded, recording will be disabled for a
period of time defined by the user.
Parameter
Number of
triggers
Time interval
Disabling time
Disturbance records can be created in the following ways:
Continuously:
Allowed values
0 ... 12
0 ... 60 s
1 ... 60 min
RPV311
Increment
1
1 s
1 min