74

Figure 29: Adding and editing a power threshold

A The <A
> button allows user to apply the hold time or the hysteresis for all
PPLY ALL
thresholds.
B The <R
> button allows user to delete the threshold.
EMOVE
Power Swing, Voltage Oscillation and Frequency Oscillation:
The parameters that are configurable in Power Swing,Voltage Oscillation and
Frequency Oscillation threshold are: Oscillation magnitude (in MVA, PU and Hz),
Oscillation time (in seconds) and Hysteresis (in percentage). The Operator scroll box
can only be set to Greater Than. To trigger, the RPV311 uses a fixed band-pass filter
adjusted at 0.1 Hz to 5 H
RPV311