Watchdog; Rpv311 Troubleshooting; Ready In Processing Module Does Not Light Up; Alarm In Processing Module Lights Up - GE RPV311 Technical Manual

Distributed multifunction fault recorder
Table of Contents

Advertisement

Chapter 16 – Maintenance and Troubleshooting
1.4

Watchdog

2

RPV311 Troubleshooting

2.1

Ready in processing module does not light up

2.2

Alarm in processing module lights up

RPV311-TM-EN-7
Only clean the equipment with a lint-free cloth dampened with clean water. Do not
use detergents, solvents or abrasive cleaners as they may damage the product's
surfaces and leave a conductive residue.
The RPV311 presents an internal watchdog algorithm. This algorithm verifies, every
second, if the device's system is responding correctly. Case the system does not
respond the device performs a hardware reboot while the output relay 1 signals that
the RPV311 is off.
The unit continuously executes an internal auto-diagnosis routine. The result of this
diagnosis is reflected by the Ready led on the front panel of the unit, on the status
page of the Web Interface and by the failure relay (normally closed contact) on the
back panel of the unit.
If the local interface does not operate, the Ready indicator does not light up. In this
case, the processing module must be sent for technical assistance.
If the indicator is lit up, the equipment may have some of the problems described
below. To identify the problem that generated the alarm, access the status of
equipment and links in the Web Interface, as shown in Chapter 5: Operation.
Problem
Transmission of
configuration
Internal failure
Before cleaning the device, ensure that all AC
and DC supplies and transformer connections
are isolated, to prevent any chance of an
electric shock while cleaning.
Normal behavior, no action should
be taken
Equipment is not operating, replace
the processing module
RPV311
Solution
249