GE RPV311 Technical Manual page 177

Distributed multifunction fault recorder
Table of Contents

Advertisement

RPV311
1.4.3
The Traveling Wave Fault Location
RPV311-TM-EN-7
Below is an example of the power line configuration:
<?xml version"1.0" encoding="UTF-8"?>
<line>
<length>248.5993</length>
<k1>248.28</k1>
<k2>0.98658</k2>
<terminal _ a>substation1,RPV311-TW,term _ a</terminal _ a>
<terminal _ b>substation2,RPV311-TW,term _ b</terminal _ b>
<towers>
<tower id"0" name="Pórtico substation1">
<latitude>-13.82689</latitude>
<longitude>-48.29898</longitude>
<distance>0</distance>
</tower>
<tower id"1" name="T1">
<latitude>-13.82665</latitude>
<longitude>-48.29866</longitude>
<distance>43.7</distance>
</tower>
...
<tower id="581" name="Pórtico substation2">
<latitude>-15.923331</latitude>
<longitude>-48.175103</longitude>
<distance>248593.3</distance>
</tower>
</towers>
</line>
The graphical interface must be open, double click the Fault Locator icon on the
desktop.
The Fault Locator interface is shown in
Chapter 12 – RPV Tools
Figure 79.
177