The I
text field allows user to enter a single code for the circuit being defined
DENTIFIER
(maximum 15 characters). No editing allowed;
The W
scroll box allows selecting a number of elements used for measuring (1, 2,
IRING
3 or 4). No editing allowed;
Selecting the 3-
PHASE CIRCUIT SYNTHESIS
enabled. It is only possible to select 3-phase circuit synthesis in a 1 element circuit
(phase A, B, or C);
The I
scroll box allows user to select the inputs to which each measuring
NPUTS
element is connected. No editing allowed;
The N
text field allows user to enter a circuit rated current;
OMINAL VALUE
The F
REQUENCY REFERENCE
The R
text fields allows user to enter ratio of power transformers for each input
ATIO
.
Once the circuit is created, it appears in the configuration interface menu. When
selecting the circuit, a screen shows the characteristics of the circuit selected, as
shown in
Figure
23. It is possible to edit some parameters, such as nominal value,
frequency reference, and transformation ratio.
The frequency is calculated individually for each circuit as long as the magnitude of
the current is over 10% of the nominal magnitude configured in the Current window
of the chosen Voltage Circuit. The frequency track occurs within the range of
Nominal Frequency ±5Hz.

Figure 23: Adding and editing current circuits

A The <R
> button allows user to rename the circuit.
ENAME
B The <R
> button allows user to delete the circuit.
EMOVE
check box, the 3-phase circuit synthesis is
scroll box allows user to select a reference voltage circuit;