15.1.1 Connection diagram of the DC transducer inputs ± 20 mA
Figure 128: Connection Diagram of DC Transducer Inputs ± 20 mA
16

Current Clamps

RPV311-TM-EN-7

Figure 127: Internal Jumper

Place the board back in the case.
Secure the case by screwing the back panel and connecting the terminals cables.
Connections shall use insulated flexible wires of 1.5 mm² cross section, 8 mm ring
terminals, and M3 holes.
Before making the electrical connection, make sure the signal is applied in
accordance with the technical specifications of the equipment. For information about
DC transducer input specifications, see Chapter 17: Technical Specifications.
In order to operate the equipment with the current clamps connection, it is necessary
that the RA33x have the proper analog input board (CORTEC description: Analog
Input 100 mA / 115 V).
As the measuring principle is based on current, the RA's internal jumper needs to be
set to current mode. To do so, follow the procedure described on the topic 13 Analog
Current Inputs.
RPV311