Key Features - GE RPV311 Technical Manual

Distributed multifunction fault recorder
Table of Contents

Advertisement

Chapter 1 – Introduction
Figure 2: Location of Serial Number, Part Number and specifications
5

Key Features

RPV311-TM-EN-7
The RPV311 plus RA33x acquisition modules solution presents the following key
features:
Acquisition system:
16-bit opto-isolated analog-to-digital converters, independent for each
channel (50/60 Hz channels);
256 points-per-cycle sampling rate (50/60 Hz channels);
Frequency response of DC to 3.0 kHz;
8-bit opto-isolated analog-to-digital converters, independent for each
channel (high-speed channels);
MHz sampling frequency (high-speed channels);
Internal time skew compensation;
Sampling rate synchronized to external IRIG-B reference;
Channel capacity:
Up to 64 analog inputs (voltage, current, DC transducers);
Up to 12 high-speed analog inputs for Traveling Wave Fault Location;
Up to 256 digital inputs;
RPV311