Continuous Recording; Disturbance Recorder; Figure 32: Fault Recorder - Continuous Recording Configuration Section - GE RPV311 Technical Manual

Distributed multifunction fault recorder
Table of Contents

Advertisement

Chapter 4 – Configuration
10.2

Continuous Recording

Figure 32: Fault recorder – continuous recording configuration section
11

Disturbance Recorder

78
In this section, shown in the figure below, is possible to configure the equipment's
continuous recorder.
A The E
check box allows user to enable the continuous fault recording
NABLED
feature.
B The Q
scroll box allows user to select the derived quantity of continuous
UANTITY
disturbance records.
C The <D
> button allows user to deselect magnitudes selected.
ESELECT ALL
It is possible only to enable the fault continuous recorder if the disturbance
continuous recorder is disabled. It is not possible to use both recorders
simultaneously.