If the card user has group choice all groups available to the user will be displayed on the keypad. The user
must select the groups to be set/unset/part set using the appropriate number keys, as per normal PIN users.
If the card user has no group choice then the card held setting function will commence automatically.

Unsetting the System with Proximity Cards

The system or groups can be unset using proximity cards with the MAX or KeyProx modules.
If the unsetting procedure has been started by activating a Final or Entry zone then, swiping the card will unset
the system. If the card user has group choice then, only the group assigned to the Final or Entry zone will be
unset. All other groups available to the user will be displayed on the programmed/selected keypad or keyprox.
NOTE: The MAX or keyprox module must have common groups to the proximity card user to allow the
card held function to be activated.

Cancelling and Resetting Alarms and Alerts

Following an alarm, sounders and strobes are activated. When a fault condition occurs in the unset state, an
alert condition is activated. This consists of an intermittent beep at the keypad and/or a visual alert on the
keypad. Following each alarm activation, the alarm must be cancelled and the Galaxy reset. The activation is
cancelled by entry of any valid user code (type 2.2 and above) assigned to the group that has alarmed or by
presentation of a valid proximity card to a reader or keyprox. The alarm sounders, Bell and Strobe outputs
are silenced and the keypad displays information on the zones or faults that have been activated. Use the A>
and <B keys to scroll through multiple activations.
If the user code entered is not of a sufficient level to reset the Galaxy, the keypad displays the message CALL
MANAGER RESET REQUIRED or CALL ENGINEER RESET REQUIRED (parameter 51.63 =
Banner Alerts must be enabled), depending on the type of alarm and level of reset required.
The Galaxy is reset by entering a valid user code assigned to the group that has alarmed, with the appropriate
reset level for the type of alarm that has activated — System, Tamper or PA (refer to option 51.6 =
PARAMETERS.System Reset, 51.7 = PARAMETERS.Tamper Reset and 51.22 =
PARAMETERS.PA Reset or 51.65 = PARAMETERS.Reset Levels). The keypad displays informa-
tion on the zones that have been activated during the alarm.
NOTE: If a tamper alarm has activated (zone or module) then the system cannot be reset until the tamper
condition is restored.
On the next setting of the Galaxy, if any of the zones that were opened during the previous alarm have not
closed since the alarm activation, then the system is prevented from setting. The addresses of the open zones
are displayed on the keypad; there is no sounder activation. Closing the zones permits the setting procedure to
start.
NOTE: This is not the same as open zones being indicated on the keypad; these are accompanied by rapid
tones on the Entry/Exit Horn.
Card Setting