Galaxy 3 Series Programming Manual
1 = Trigger
Press the ent key to display the first trigger event; the keypad shows the trigger, the trigger status and the
groups assigned.
To modify the trigger event select the required event using the A and B keys and press the ent key. The
1=Status option is then displayed. If the status requires to be modified press the ent key.
1 = Status
To program the status to On press 1, to set it to Off press 0. Alternatively use the A/B keys to toggle
between On and Off. To accept the new status, press the ent key. This will automatically return the display
to the previous menu level.
2 = Groups
If groups have been enabled on the system (refer option 63.1), then the groups can be assigned to each
event trigger. This means that the events have to occur in assigned groups before they are signalled. To
modify the groups assigned to a specific trigger press the ent key from the 2=Groups menu option. The
display will show the groups and indicate whether it is assigned (Y) or not assigned (N) to the group. To
assign or unassign a group from a specific trigger press the number key corresponding to the group
number. The display will show the new status. To accept the new status, press the ent key and return to the
previous menu level. If the Galaxy panel supports more than 8 groups use the A and B keys to scroll
through all available groups.
2 = Account No.
This option is required to assign a unique account number to the events signalled to Alarm Monitoring. This
data must be entered before any events are sent to Alarm Monitoring via this option. The account number can
be a maximum of 6 digits. Press the ent key to save the programming and return to the previous menu level.
3 = IP Address
To programme a new or modify the Alarm Monitoring IP address use the B key to erase any existing pro-
gramming and enter the new IP address to which the events are to be sent. Press ent to save the new address
and return to the previous menu level.
4 = Port No.
To programme a new port number use the B key to erase any existing programming and enter the new port
number. Press the ent key to save the new address and return to the previous menu.
7 = Heartbeat
The Ethernet module supports path supervision to ensure the alarm transmission paths are available to transmit
event when required. This option, if programmed determines the frequency, which the alarm transmission paths
are checked.
1 = Interval
Enter the interval within which a path supervision signal (heartbeat) must be received from each alarm trans-
mission path (refer option 56.4.7.2 Line Fail – Signalling Path). If a heartbeat is not received within the pro-
grammed interval a line fail condition will be activated in the panel. The Line Fail event will indicate which path
has failed (Primary, Secondary or Alarm Monitoring).
The default period is 30 minutes.