Honeywell Galaxy 3-48C Programming Manual page 165

Hide thumbs Also See for Galaxy 3-48C:
Table of Contents

Advertisement

Galaxy 3 Series Programming Manual
3 = Open Timeout
This is the period following the user card swipe that the door can remain open when gaining access. If the
door remains open longer than the period assigned to the Open Timeout, then an alarm occurs.
NOTE: If the Open Timeout is programmed as 0 seconds, then the door can remain open indefinitely
without resulting in an alarm being activated.
On entering the Open Timeout parameter, the current value is displayed; assign the required time within the
range 00 – 60 seconds, the default time is 10 seconds. Press the ent key to save the programming and return
to the previous menu level.
NOTE: Pressing the A key increases the time by one second increments, the B key decreases the time in one
second decrements.
4 = Groups
1=MAX Groups
On selecting the MAX Group option, the group currently allocated to the MAX is displayed. Pressing the
group number toggles the group assigned to the MAX.
Galaxy 520
The Galaxy 520 has 32 groups; these are displayed on the MAX in block of 8 groups, sub-divided into A, B,
C and D. Use the A or B key to move between the group blocks; press keys 1 – 8 to assign the relevant
groups in each block to the MAX.
When the required groups have been assigned to the user, press the ent key to accept the programming and
return to the previous menu level.
Group Name Display
When viewing the groups assigned to the MAX, simultaneously pressing the # and
individually. The keypad displays the number, name and the assigned status of each group on the particular
MAX being displayed. Press the # key to toggle the status of the group. To move to another group press the
A or B keys or enter the number of the group directly.
2=Group Restriction
Each MAX module can be assigned selected groups using the Group Restriction option. This group restric-
tion affects the operation of the MAX and MicroMAX readers for both access and card held functions. A
card can only be used at a reader if there are common groups between them. By default each reader is as-
signed to all groups on the system. Groups can be removed as required to restrict the operation of the MAX
reader.
NOTE: Each MAX card can be assigned a single menu function (refer to option 42 = CODES). Activating
this function with a card that is assigned to all groups, on a MAX that is only assigned to a single
group, results in the function operating on all of the card's groups. The MAX function is not re-
stricted to the groups assigned to the MAX, it is restricted to the groups assigned to the card, as
long as there is one group common to both. This means that a MAX assigned only to group 1, for
example, can be used to activate the MAX function on groups 1, 2, 3 and 4 by a card with all of
these groups allocated. The groups are assigned to the MAX card using option 42 = CODES.
63 - Options (cont'd)
159