51 - Parameters (cont'd)
46 = Zone resistance
RIOs rev 1.2 and Smart PSUs rev 0.7 and above allow the zones to be programmed, with different resistance
ranges for zone status activation. This feature allows selection of End Of Line or Double Balanced zone
resistance types. The on-board zones can also be modified using this feature.
The "EOL/Dbl. Bal." resistance types are selectable from this option. The default value is Double Balanced.
There are six preset pre-programmable resistance configurations:
1 = Preset 1 (BAL); 2 = Preset 1(EOL); 3 = Preset 2 (BAL); 4 = Preset 2 (EOL); 5 = Preset 3 (BAL);
6 = Preset 3 (EOL)
The tables that follows shows the resistance windows for each type:
Tamper S/C
Low Res
Normal
High Res
Open
Masked
Tamper O/C
Tamper S/C
Low Res
Normal
High Res
Masked
Open
When selected, this will be the zone resistance range used by every zone on the system. Each zone on the
system can be further customised to a specific preset by using menu option 52.9, Resistance Select.
Preset 1 - 1k
0 - 800
800 - 900
900 - 1200
1200 - 1300
1300 - 12000
12000 - 15000
15000 - infinity
Table 10. Preset value upper limits - double balanced
Preset 1 - 1k
0 - 800
800 - 900
900 - 1200
1200 - 1300
1300 - 12000
12000 - infinity
Table 11. Preset value upper limits - end of line
Galaxy 3 Series Programming Manual
Preset 2 - 2k2
Preset 3 - 4k7
0 - 1800
1800 - 2000
2000 - 2500
2500 - 2700
2700 - 12000
6500 - 19000
12000 - 15000
19000 - 22000
15000 - infinity
22000 - infinity
Preset 2 - 2k2
Preset 3 - 4k7
0 - 1800
1800 - 2000
2000 - 2500
2500 - 2700
2700 - 12000
12000 - infinity
19000 - infinity
64
0 - 3700
3700 - 4200
4200 - 5500
5500 - 6500
0 - 3700
3700 - 4200
4200 - 5500
5500 - 6500
6500 - 19000