Honeywell Galaxy 3-48C Programming Manual page 47

Hide thumbs Also See for Galaxy 3-48C:
Table of Contents

Advertisement

Galaxy 3 Series Programming Manual
2 = Assign Groups
This function determines which of the groups are affected by the programmed holiday periods.
On selecting the Assign Groups option, the groups currently assigned to the programmed holiday periods are
indicated by a Y below the group; an N is displayed below the unassigned groups. All groups default to Y.
Pressing the group number toggles the group status. When the required groups have been assigned to the
holidays, press the ent key to accept the programming and return to the previous menu level.
Galaxy 3-520
The Galaxy 520 panel has 32 groups; these are displayed on the keypad in blocks of eight groups, sub-
divided into A, B, C and D:
Press keys 1 – 8 to assign the relevant groups in each block to the user.
3 = Early Open
If the Early Open option (45.4.2) is enabled, the Lockout OFF time (refer to option 65 = TIMERS) for
the following day is brought forward by the number of minutes (0 – 240) programmed in parameter 44 =
Early Open. This allows the system to be manually unset earlier than normal.
1 = Early Times
This function displays the time that the system can be manually unset on the following day; this time is the
Lockout OFF Time minus the Early Open period and is displayed in the 24 hour format.
If groups have been enabled, the early opening time for each of the groups enabled for early opening in the
Early Open option can be viewed by pressing the A or B keys
This function only displays the early time if the Early Open option is enabled; if this option is disabled or if no
groups have been enabled, the message NO ENTRIES is displayed.
2 = Early Open
Type 3. 6 Users and Engineer when Groups are Disabled
If groups have not been enabled on the system, the programming of the Early Open option is identical for
type 3.6 users and the engineer; the option permits early opening to be disabled or enabled:
0
=
Disabled (default) — early opening not permitted;
1
=
Enabled — early opening permitted.
Select the required status and press the ent key to accept the programming and return to the previous menu.
Engineer Mode with Groups Enabled
If groups have been enabled (option 63 = OPTIONS + early open permitted), then the groups can be
individually enabled to permit early opening.
4 = Timers
This option allows Timer A and Timer B to be switched on and off as required. If a Timer is set to off, the
operation of the Timer is suspended; this option cannot be used to alter the programmed times. Both timers
default to 0 = Off. To switch the timers on, select the required timer and change the setting to 1 =On.
The Timer Status can also be altered through menu option 65.1 by the engineer only.