Galaxy 3 Series Programming Manual
There are five stages to programming the Autoset function:
1. Autoset Status
0 = Off (default)
1 = On
2 = Monitor - if selected, the setting and unsetting of the group is monitored:
if not set manually before the On time, then the Set Late output is activated
if unset before the Off time, then the Unset Early output is activated.
2. Prewarning
1 = Period
0 – 50 minutes (default 30 minutes):
2 = Audible (this can be turned ON or OFF)
This option determines the warning period given to users prior to the system autosetting. Outputs programmed
as Prewarning activate during the prewarning period. The output normally emits a constant tone, however if
an extension is not possible, then a pulsed tone is emitted and prewarn activates at the Autoset time. At the
end of the prewarning period, the system begins the timed setting procedure.
NOTE: Pressing the esc key at any time during the prewarning resets and restarts the prewarning count-
down. If more than one group is in the prewarning period, each group can be viewed by pressing *
and > or * and <.
3. Extension
0 – 400 minutes (default 30 minutes):
An autoset Extension can be assigned to each group on the system - programmed with different values per
group. Entering a user code during the Prewarning delays the autosetting by the period assigned to the
Extension.
NOTE: The Late Working option (refer to option 45 = TIMERS) authorizes an Extension in advance of
the Prewarning period.
Late Set appears if the system is not set after prewarn time plus 300 seconds (longest possible exit delay)
An Extension cannot be granted once the timed setting procedure begins.
4. Force Set
0 = Off (default)
1 = On
As a factory preset, any zone that is open at the start of the setting procedure - except Final, Exit, Entry, or
Push Set, (or Secure Final or Part Final when acting as a Final) - is omitted by the autoset routine whether
or not it is omittable. If one of the above listed zones is open and is non-omittable, on expiry of the time
programmed in the Fail-to-Set parameter the Fail-to-Set outputs are activated along with a full alarm.
65 - Timers (cont'd)
169