Constant Current Source Mode Procedure; Figure 5-1: Current Loop Test Connections - Honeywell SLG 700 User Manual

Smartline level transmitter guided wave radar
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

5.3.2 Constant Current Source Mode Procedure

1. Refer to
Figure 5-1
output current loop.
2. Establish communication with the Transmitter. For these procedures, the values of components in
the current loop are not critical if they support reliable communication between the Transmitter
and the Toolkit.
3. On the Toolkit, display the Output Calibration box.
4. In the Output Calibration box, select the Loop Test button; the LOOP TEST box will be
displayed.
5. Select the desired constant-level Output: 0%, 100%, or Other (any between 0% - 100%).
6. Select the Set button. A box will be displayed asking Are you sure you want to place the
transmitter in output mode?
Revision 7

Figure 5-1: Current Loop Test Connections

for test connections. Verify the integrity of electrical components in the
SLG 700 SmartLine Level Transmitter User's Manual
Page 115

Advertisement

Table of Contents
loading

Table of Contents