Flange mount
3.2.9.1
To mount a flanged transmitter, bolt the transmitter's flange to the flange pipe on
the wall of the tank.
Step
On insulated tanks, remove enough insulation to accommodate the flange
extension.
1
Note: It is the End User's responsibility to provide a flange gasket and
mounting hardware that are suitable for the transmitter's service condition.
Ensure correct functionality:
2
To ensure a reliable electrical contact between the tank and transmitter, use
unpainted, metal bolts.
Revision 7

Figure 3-23: Flanged tank connection

SLG 700 SmartLine Level Transmitter User's Manual