This table describes the Advanced Display menu's "Monitor" sub-menu. All items are Read-
Only. Refer to troubleshooting for resolutions.
<Return> Return to the Level 1 menu
Level 2
Level 3
<Return>
Active Diags (R)
Sensor Module (R)
Comm Module (R)
Sensor Comm (R)
Measurement (R)
Reset Required (R)
Critical Diag
Detail Diag
Sensor Int RAM (R)
Sensor Ext RAM (R)
Sensor Flash CRC (R)
Sensor Pwr Vosc (R)
Sensor Pwr 2.5V (R)
Sensor Pwr 3.3V (R)
Sensor Pwr Accum (R)
Sensor Code Flow (R)
Sensor Oscillator (R)
Factory Mode (R)
Low Power Mode (R)
Revision 7
Table 4-8: Monitor sub-menu
Status
# #
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
Yes
No
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
Yes
No
Yes
No
SLG 700 SmartLine Level Transmitter User's Manual
Description
FAULT: There is a problem with the Sensor.
FAULT: There is a problem with the
Communications Module (HARTor FF), There
are one of the following failures:
RAM Failure: Restart the device. If error
continues, replace the HART communication
board.
ROM Failure: Reflash / reload the HART
firmware. If error continues, replace the HART
communication board.
V
Failure: If the power accumulator (PA) fault
CC
is not detected, change the HART
communication board.
FAULT: There is a problem with the interface
between the Sensor and the Electronics Module.
FAULT: There is a problem with the PV
measurement.
FAULT: A parameter has been changed that
requires a transmitter restart.
Yes: All menu items to Factory Mode are
available.
No: The menu options end with Detail Diag.
FAULT: Sensor Internal RAM is Bad
FAULT: Sensor Internal RAM is Bad
FAULT: Sensor Flash CRC is Bad
FAULT: The Vosc measurements are out of
range, resetting the device if the problem
persists, replace the Sensor Housing.
FAULT: Sensor Power Supply 2.5V is Bad
FAULT: Sensor Power Supply 3.3V is Bad
FAULT: Power Accumulator Board is Bad
FAULT: Sensor Execution is not working as
intended
FAULT: Sensor Oscillator Control Status is Bad
Yes: Sensor is in Factory Mode
No: Sensor is in User Mode
Yes: Sensor is in low power mode