Figure 3-6: SLG726 flanged process connection, probe nut installation position, mm [in]

3.2.4.2
Wire probe assembly
Wire probes can be supplied with an optional end weight.
Step
Fully thread the nut onto the central conductor. Using a lock washer, thread the
wire swage on to the central conductor. Torque the nut against probe and lock
washer to secure the connection.
Note:
1
Tighten the wire stud and nut to the following torque:
If applicable, insert wire probe into end weight. Tighten the 3 set screws to
secure end weight to wire probe
2
Note: Torque set screws to 6Nm (4.4ft-lbs)
Note: For flanged SLG726 models, ensure the nut does not intrude into the bore of the
process connector. See Figure 3-6 for more information.
Revision 7
SLG720 6.0Nm (4.4ft-lbs)
SLG726 15Nm (11ft-lbs)
SLG 700 SmartLine Level Transmitter User's Manual
Action
Page 39