Diagnosing Slg720 Coaxial Probe Misassembly - Honeywell SLG 700 User Manual

Smartline level transmitter guided wave radar
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Active Diags
Supply Voltage
Elec Module Temp
PV Range
Sensor Over Temp
Prod Sgnl Str
Prod Sgnl Qlty
Upper Product Signal Strength
Upper Product Signal Quality
Lower Product Signal Strength
Lower Product Signal Quality
Blk Dist Hi Zone
Blk Dist Lo Zone

6.2 Diagnosing SLG720 Coaxial Probe misassembly

Revision 7
Displays a numeric value of the
current count of non-critical status
bits that have been set.
Displays a status of the power
voltage.
Displays a status of the sensor
electronics.
Displays a status of the Loop PV is
within or outside the configured URV
and LRV.
Displays a status of the temperature
of the sensor electronics.
Displays a status of the quality of
the signal strength.
Displays a status of the quality of
the signal.
Displays the status of the strength of
the signal monitoring the upper
product.
Displays the status of the quality of
the signal monitoring the upper
product.
Displays the status of the strength of
the signal monitoring the lower
product.
Displays the status of the quality of
the signal monitoring the upper
product.
Bulk Distance High Zone
The distance within the upper
blocking range.
Bulk Distance Low Zone
The distance within the lower
blocking range.
SLG 700 SmartLine Level Transmitter User's Manual
N/A
Ensure the voltage on the
terminals are within
operational specifications.
Bring the sensor within range
and reset the power.
PV Out of Range
Any of the following
conditions can cause this
failure:
1.
Sensor Overload or Fault
or Redundant
Characterization
Calculation Error.
2.
Check range and, where
required, replace
transmitter with one that
has a wider range.
Sensor may have been
damaged.
3.
Check the transmitter for
accuracy and linearity.
4.
Replace the sensor and
recalibrate, where
required.
If the temperature is outside
the configured range, bring
the temperature within the
range and reset or repower.
Read the echo curve and
configure the algorithm and
the dielectric constant.
Theses parameters display
physical locations within the
container where
measurements are not
accurate.