Section 14
Basic IED functions
IEC09000063 V1 EN-US
Figure 169: Connection of the function to external circuits
The above example also includes four binary output signals, for confirmation of which group is active.
14.4

Test mode functionality TESTMODE

14.4.1

Identification

Function description
Test mode functionality
14.4.2

Functionality

When the Test mode functionality TESTMODE is activated, all the functions in the IED are
automatically blocked. Activated TESTMODE is indicating by a flashing yellow LED on the local HMI.
It is then possible to unblock every function(s) individually from the local HMI to perform required
tests.
When leaving TESTMODE, all blockings are removed and the IED resumes normal operation.
However, if during TESTMODE operation, power is removed and later restored, the IED will remain
in TESTMODE with the same protection functions blocked or unblocked as before the power was
removed. All testing will be done with actually set and configured values within the IED. No settings
will be changed, thus mistakes are avoided.
Forcing of binary output signals is only possible when the IED is in test mode.
380
ACTIVATE GROUP 4
ACTIVATE GROUP 3
ACTIVATE GROUP 2
ACTIVATE GROUP 1
IOx-Bly1
Æ
IOx-Bly2
Æ
IOx-Bly3
Æ
IOx-Bly4
Æ
IEC 61850
identification
TESTMODE
© 2021 Hitachi Energy. All rights reserved.
ACTVGRP
ACTGRP1
GRP1
ACTGRP2
GRP2
ACTGRP3
GRP3
GRP4
ACTGRP4
SETCHGD