1MRK 511 557-UEN Rev. A
Name
Values (Range)
Threshold9
DebounceTimeOn9
DebounceTimeOff9
OscillationCntOn9
OscillationCntOff9
OscillationTimeOn9
OscillationTimeOff9
Threshold10
DebounceTimeOn10
DebounceTimeOff10
OscillationCntOn10
OscillationCntOff10
OscillationTimeOn10
OscillationTimeOff10
Threshold11
DebounceTimeOn11
DebounceTimeOff11
OscillationCntOn11
OscillationCntOff11
OscillationTimeOn11
OscillationTimeOff11
Threshold12
DebounceTimeOn12
DebounceTimeOff12
OscillationCntOn12
OscillationCntOff12
OscillationTimeOn12
OscillationTimeOff12
4.2

Binary outputs

4.2.1
Binary outputs
The PSM02 or PSM03 module provides 10 output relay contacts. 6 of these are rated for making and
carrying high currents, and three of these include circuits for trip coil supervision. The remaining 4
relay contacts are intended for signaling; one of them is internally hardwired to indicate Internal Relay
Failure (IRF).
The BIO module provides 9 output relay contacts. Out of these, 3 are rated for making and carrying
high currents. The remaining 6 contacts are intended for signaling; some of them share a common
terminal, see the connection diagram for details.
Technical Manual
Unit
15 - 221
-
0.0000 - 0.1270
-
0.0000 - 0.1270
-
0 - 255
-
0 - 255
-
0.000 - 600.000
-
0.000 - 600.000
-
15 - 221
-
0.0000 - 0.1270
-
0.0000 - 0.1270
-
0 - 255
-
0 - 255
-
0.000 - 600.000
-
0.000 - 600.000
-
15 - 221
-
0.0000 - 0.1270
-
0.0000 - 0.1270
-
0 - 255
-
0 - 255
-
0.000 - 600.000
-
0.000 - 600.000
-
15 - 221
-
0.0000 - 0.1270
-
0.0000 - 0.1270
-
0 - 255
-
0 - 255
-
0.000 - 600.000
-
0.000 - 600.000
-
© 2021 Hitachi Energy. All rights reserved.
Step
Default
1
65
0.0001
0.0050
0.0001
0.0050
1
0
1
0
0.001
0.000
0.001
0.000
1
65
0.0001
0.0050
0.0001
0.0050
1
0
1
0
0.001
0.000
0.001
0.000
1
65
0.0001
0.0050
0.0001
0.0050
1
0
1
0
0.001
0.000
0.001
0.000
1
65
0.0001
0.0050
0.0001
0.0050
1
0
1
0
0.001
0.000
0.001
0.000
Binary inputs and outputs
Description
Threshold in percentage of station
battery voltage for input 9
Debounce time On for input 9
Debounce time Off for input 9
OscillationCountOn for input 9
OscillationCountOff for input 9
OscillationTimeOn for input 9
OscillationTimeOff for input 9
Threshold in percentage of station
battery voltage for input 10
Debounce time On for input 10
Debounce time Off for input 10
OscillationCountOn for input 10
OscillationCountOff for input 10
OscillationTimeOn for input 10
OscillationTimeOff for input 10
Threshold in percentage of station
battery voltage for input 11
Debounce time On for input 11
Debounce time Off for input 11
OscillationCountOn for input 11
OscillationCountOff for input 11
OscillationTimeOn for input 11
OscillationTimeOff for input 11
Threshold in percentage of station
battery voltage for input 12
Debounce time On for input 12
Debounce time Off for input 12
OscillationCountOn for input 12
OscillationCountOff for input 12
OscillationTimeOn for input 12
OscillationTimeOff for input 12
GUID-5E9466BB-B479-4CDF-9FAD-7D0C6E2D0789 v2