Section 12
Monitoring
Last operation time alarms
The operation times of the last operation are compared against their expected values, which are
either set values or calculated average values, depending on the AlmTolSetSel setting. Refer
305
for detailed description.
Table 305: Reference values for checking actual switching times (X = L1 / L2 / L3)
AlmTolSetSel
setting
AlmTolOnDef
Val
AlmTolOnAvg
CalVal
Any deviation of more than AlmTolRange from the expected value will raise an alarm. The only
exception is the first operation when comparison to calculated average values (AlmTolOnAvgCalVal)
is selected:
Here, an alarm will be raised if the difference between phases exceeds the AlmTolRange setting.
344
Primary
Primary
contact
contact
closing time
opening time
DefaultPriClTi
DefaultPriOp
meX setting
TimeX setting
CLAVGPRIX
OPAVGPRIX
© 2021 Hitachi Energy. All rights reserved.
NO (52a)
NO (52a)
closing time
opening time
DefaultNOClT
DefaultNOOp
imeX setting
TimeX setting
CLAVGNOX
OPAVGNOX
1MRK 511 557-UEN Rev. A
GUID-DC5703CC-3AF0-4A20-BBCD-CE0ACC2A253D v2
Table
NC (52b)
NC (52b)
closing time
opening time
DefaultNCClT
DefaultNCOp
imeX setting
TimeX setting
CLAVGNCX
OPAVGNCX
Technical Manual